Wire Sizing Calculator

NEC ampacity tables and voltage drop calculations

Wire Size Calculator

Voltage Drop Calculation

Recommended Wire Size

Enter load current to see recommendations

Important NEC Considerations

Table 310.16 (310.15(B)(16)): Allowable ampacities of insulated conductors rated up to and including 2000V, not more than three current-carrying conductors in raceway, cable, or earth.

Temperature Correction: Apply correction factors from Table 310.15(B)(2)(a) for ambient temperatures other than 30°C (86°F).

Adjustment Factors: Apply adjustment factors from Table 310.15(B)(3)(a) when more than three current-carrying conductors are in raceway or cable.

Continuous Loads: Size conductors at 125% of continuous loads per NEC 210.19(A)(1).

Voltage Drop: NEC recommends maximum 3% voltage drop on branch circuits and 2% on feeders (5% total).

Termination Ratings: Check equipment termination temperature ratings. Most equipment is rated for 75°C.